Accessing the Damper Characterization Table
Manually Entering Damper Characterization Data
While not ideal, the damper characterization data can be calculated and entered manually in the AFMS Table. This should only be done if — in the allotted time for Setting Up an AFMS — the ΔT is unlikely to be greater than the Min Delta Temp for the duration of Learning Mode. In that case, for reliability, running Learning Mode at a later available time is still recommended.
Accessing the AFMS Table
Select the Tune tab.
Interpreting the AFMS Table
Label | Description |
---|---|
OA Fraction Flow |
Percentage (expressed as a decimal) of the supply airflow that is outside airflow at the given outside air damper position |
Diff Pressure (pressure assist application only) |
The pressure differential (in inches of water column) at the given outside air damper position See the AFMS documentation for pressure assist information. |
Outside Air Closed |
Outside air damper at closed position |
Outside Air 5 |
Outside air damper at 0–5% open |
Outside Air 10 |
Outside air damper at 5–10% open |
Outside Air 15 |
Outside air damper at 10–15% open |
Outside Air 20 |
Outside air damper at 10–20% open |
Outside Air 30 |
Outside air damper at 20–30% open |
Outside Air 40 |
Outside air damper at 30–40% open |
Outside Air 50 |
Outside air damper at 40–50% open |
Outside Air 60 |
Outside air damper at 50–60% open |
Outside Air 70 |
Outside air damper at 60–70% open |
Outside Air 80 |
Outside air damper at 70–80% open |
Outside Air 90 |
Outside air damper at 80–90% open |
Outside Air 100 |
Outside air damper at 90–100% open |
Calculating the damper characterization data
Use the %OA equation found in ASHRAE Standard 111, section 7.6.3.3: "Flow Rate Approximation by Temperature Ratio".
Note: Find ASHRAE Standard 111 on this page of read-only versions of ASHRAE standards.
Note: See Controlling Airflow with an AFMS for how to set the outside air damper to the required positions for the measurements.
Note: See Monitoring with an AFMS for where to find the sensor readings.
Continue to Operating an AFMS.
Verifying the Damper Characterization Data
Should the damper characterization data require verification, measurements should only be made using NIST-traceable instruments and the method described in ASHRAE Standard 111. (See the details in Manually Entering Damper Characterization Data.)