How to Calibrate the AFMS's Sensors
-
Go to AFMS
, then select the Device Name of the AFMS controller. -
Select the Tune tab.
-
Under Offset for Supply Air Flow, enter the CFM offset (determined by a TAB technician) for the supply air pressure transducer.
-
Under Multiplier for Supply Air Flow, enter the multiplier (determined by a TAB technician) for the supply air pressure transducer.
-
Under Offset for Outside Air Temp, Return Air Temp, and Mixed Air Temp, enter the °F offsets (determined by a TAB technician) for the outside, return, and mixed air temperature sensors.
-
Select Save.
Note: For more information on the AFMS's sensors, see the Airflow Measurement System Selection Guide, found on any AFMS controller's product page.
Continue to Running AFMS Learning Mode.