Calibrating the AFMS's Sensors

  1. Go to AFMS , then select the Device Name of the AFMS controller.

  2. Select the Tune tab.

  3. Under Offset for Supply Air Flow, enter the CFM offset (determined by a TAB technician) for the supply air pressure transducer.

  4. Under Multiplier for Supply Air Flow, enter the multiplier (determined by a TAB technician) for the supply air pressure transducer.

  5. Under Offset for Outside Air Temp, Return Air Temp, and Mixed Air Temp, enter the °F offsets (determined by a TAB technician) for the outside, return, and mixed air temperature sensors.

  6. Select Save.

Note: For more information on the AFMS's sensors, see the Airflow Measurement System Selection Guide, found on any AFMS controller's product page.

Continue to Running AFMS Learning Mode.